ZL-25T FRP counter flow cooling tower engineered for 25 ton (87.92 kW) heat rejection. 19.51 m3/h water flow, 0.75 kW fan motor, 200 CMM airflow. FRP shell, ABS fan. 5 deg C approach to wet-bulb at 27 deg C design condition. Specifications: 87.92 kW heat rejection at 25 refrigeration ton, FRP counter-flow shell with 5 deg C approach to wet-bulb 27 deg C design. 200 CMM airflow at 770 mm fan diameter, 0.75 kW motor at 380V 3-phase 50 Hz, 16 kPa head loss at 19.51 m3/h design flow. Dry weight 98 kg, operating weight 500 kg. CE ISO 9001:2015 certified, IP55 Class F insulation, FRP shell with ABS fan. Counter-flow geometry with FRP shell delivers thermal performance per CTI STD-201. Fan curve: 200 CMM at 770 mm blade diameter, 0.75 kW motor at 380V 3-phase 50 Hz. Head loss 16 kPa at design flow 19.51 m3/h. Reynolds number analysis confirms turbulent flow regime across fill media, ensuring 5 deg C wet-bulb approach under design conditions. Suitable for HVAC chiller condenser and process cooling integration.