ZL-15T FRP counter flow cooling tower engineered for 15 ton (52.75 kW) heat rejection. 11.7 m3/h water flow, 0.37 kW fan motor, 140 CMM airflow. FRP shell, ABS fan. 5 deg C approach to wet-bulb at 27 deg C design condition. Specifications: 52.75 kW heat rejection at 15 refrigeration ton, FRP counter-flow shell with 5 deg C approach to wet-bulb 27 deg C design. 140 CMM airflow at 635 mm fan diameter, 0.37 kW motor at 380V 3-phase 50 Hz, 13 kPa head loss at 11.7 m3/h design flow. Dry weight 54 kg, operating weight 290 kg. CE ISO 9001:2015 certified, IP55 Class F insulation, FRP shell with ABS fan. Counter-flow geometry with FRP shell delivers thermal performance per CTI STD-201. Fan curve: 140 CMM at 635 mm blade diameter, 0.37 kW motor at 380V 3-phase 50 Hz. Head loss 13 kPa at design flow 11.7 m3/h. Reynolds number analysis confirms turbulent flow regime across fill media, ensuring 5 deg C wet-bulb approach under design conditions. Suitable for HVAC chiller condenser and process cooling integration.