ZL-10T 10 ton FRP counter flow cooling tower, maintenance tech specification, 7.81 m3/h water flow, 0.37 kW motor, 35.2 kW heat rejection

ZL-10T Cooling Tower V4 Maintenance Tech

The ZL-10T 10 Ton FRP Counter Flow Cooling Tower from Zillion delivers reliable maintenance tech performance. Key specifications include:

  • ZL-10T water chemistry: pH 6.5-9.0, Ca hardness <500 ppm
  • Conductivity <2,500 uS/cm, TSS <50 ppm
  • Quarterly fill media visual inspection (15 minutes)
  • Annual wash with descaling solution (3-4 hours)
  • Fan motor 50,000 hour bearing life (8.5 years at 16 hr/day)
  • Winter freeze protection: basin heater USD 220/year operating
  • Annual water treatment chemical cost: USD 490
  • Drift eliminator replacement: 5-year cycle

Designed for industrial-grade maintenance tech applications, the ZL-10T combines proven FRP counter flow technology with precision-engineered components for 15-20 year service life. CE / ISO 9001:2015 certified. Contact Leika at Leika@gdzillion.cn for quotation.

  • Brand:

    Dongguan Zillion
  • ItemNO:

    ZL-10T
  • Order(MOQ):

    1
  • Payment:

    T/T, L/C, Western Union, Alibaba Trade Assura
  • MarketPrice:

    $1050
  • price:

    $850/Set
  • ProductOrigin:

    China
  • Color:

    Blue + Gray (customizable)
  • ShippingPort:

    Shenzhen / Guangzhou
  • LeadTime:

    7-15 days
  • Weight:

    46
  • Size:

    High:2570mm Diameter:2900mm

ZL-10T 10 Ton Cooling Tower Maintenance Schedule | Water Quality & Fill Care Guide

ZL-10T 10 Ton Counter Flow Square FRP Cooling Tower Quick Specifications

Parameter Value
Model ZL-10T
Cooling Capacity 10 RT (35.2 kW heat rejection)
Water Flow Rate 7.81 m3/h (130 L/min)
Cooling Range 5C (37C inlet to 32C outlet at design WB 27C)
Approach to Wet-Bulb 5C at design conditions
Fan Motor 0.37 kW (0.5 HP) 380V 3-phase 50Hz
Fan Diameter 635 mm axial
Air Flow Rate 85 CMM (50,920 m3/h)
Head Loss at Design Flow 13 kPa
Tower Dimensions (H x D) 1820 x 940 mm
Dry Weight 46 kg
Operating Weight (filled) 190 kg
Noise Level 60 dB(A) at 1 m
Tower Body Material FRP (Fiberglass Reinforced Plastic)
Fan Blade Material ABS plastic
Configuration Counter Flow Square
Voltage 380V 3-phase 50Hz (customizable 220V/415V)
Certifications CE / ISO 9001:2015
Warranty 1 year (consumables excluded)

Water Chemistry Targets: Calcium Hardness 500 ppm, pH 6.5-9.0, Conductivity <2,500 µS/cm

The ZL-10T's FRP shell and ABS fan tolerate a specific circulating water chemistry envelope. Operating outside these parameters accelerates scaling, biological growth, and corrosion:

pH 6.5-9.0: Below pH 6.5, FRP resin degradation accelerates. Above pH 9.0, scale formation on fill media increases dramatically (calcium carbonate precipitation rate doubles for each 0.5 pH unit above 8.5).

Calcium hardness <500 ppm as CaCO3: Above 500 ppm, the Langelier Saturation Index (LSI) becomes positive, indicating scale-forming tendency. For cooling towers operating in hard-water regions (Midwest US, North China, Middle East), a bleed-off and chemical treatment program is essential.

Conductivity <2,500 µS/cm: High conductivity indicates dissolved solids buildup from evaporation cycles. Blowdown at 2,500 µS/cm maintains cycles of concentration at 3-5, balancing water conservation against scale risk.

Total suspended solids <50 ppm: TSS above 50 ppm causes fill media fouling and biological growth. Side-stream filtration is recommended for installations with TSS-prone makeup water.

Fill Media Cleaning: Quarterly Inspection and Annual Wash

The ZL-10T's PVC fill media is the primary heat transfer surface — fouled fill degrades approach temperature by 2-5°C within 6-12 months if untreated. Recommended maintenance protocol:

Quarterly visual inspection (15 minutes): Remove two inspection panels at the air inlet. Use a flashlight to examine fill media surface. Look for: white scale deposits (calcium carbonate), green/black biological film (algae, biofilm), or visible debris accumulation.

Annual wash (3-4 hours): Drain the basin, isolate the tower from chiller loop. Spray fill media with a descaling solution (5% inhibited hydrochloric acid or commercial cooling tower cleaner). Allow 30-minute contact time, then flush with fresh water. Re-fill basin and resume circulation.

Biological growth control: Apply algaecide (typically isothiazolinone-based) at 50-100 ppm initial dose, 10-20 ppm maintenance dose. Apply at the basin inlet during circulation for proper mixing.

Drift Eliminator Inspection: Reducing Water Loss from 3% to 0.005%

The ZL-10T's PVC drift eliminator captures water droplets entrained in the rising air stream. Properly functioning drift eliminators limit water loss to <0.005% of circulation flow. Failed or missing eliminators allow 1-3% drift loss, costing:

At 1% drift with 7.81 m³/h circulation: 0.01 × 7.81 × 24 × 365 = 684 m³/year = 684,000 liters/year wasted. At industrial water rates of USD 0.0015/liter, that's USD 1,026/year per tower in wasted water.

Maintenance procedure: quarterly visual inspection from above the eliminator (look for daylight passing through the eliminator waves — if you can see sky through the eliminator, droplets are bypassing). If damaged, replace the eliminator module (USD 45/set, 30-minute replacement time).

Fan Motor Service: 50,000 Hour Bearing Life

The ZL-10T's 0.37 kW fan motor uses sealed-for-life bearings rated for 50,000 hours at the design ambient temperature of 40°C. At 16 hr/day operation, this equates to 8.5 years of continuous service before bearing replacement.

Annual motor service includes: (1) Verify amp draw is within 10% of nameplate FLA (typically 1.2-1.5 amps for 0.37 kW motor). Higher amp draw indicates bearing wear or impeller fouling. (2) Inspect motor windings for thermal discoloration (a slight yellowing is normal; dark brown indicates overheating). (3) Verify thermal overload setting matches motor nameplate. (4) Check V-belt tension (if belt-driven configuration) at 1% deflection per 10 mm span.

Motor replacement interval: 8-10 years under normal operation. Replacement cost: USD 85 plus 1 hour labor.

Winter Freeze Protection: Critical for Cold-Climate Installations

For ZL-10T installations in climates where ambient temperature drops below 0°C, freeze protection is essential. The ZL-10T basin holds 190 liters of water at full operating level — this volume freezes within 8-12 hours at -10°C ambient if circulation stops.

Recommended freeze protection:

1. Basin heater: 1 kW electric immersion heater maintains basin water at 4-7°C. Power draw during cold weather: 4-6 hr/day. Annual electricity cost at USD 0.10/kWh: USD 150-220.

2. Continuous circulation: Operate the fan year-round with reduced water flow (50% of summer rate). Prevents ice formation on fill media and piping.

3. Drain-down option: For installations with seasonal operation (e.g., central air conditioning serving summer-only facilities), drain basin and piping before winter. Add automotive-grade antifreeze (propylene glycol, 30% concentration) for residual piping protection.

Failure to implement freeze protection typically results in cracked piping, damaged fill media, and basin cracking — USD 1,500-3,000 in repairs versus USD 220/year in basin heater operating cost.

Water Treatment Program: Chemical Dosing and Blowdown Control

A properly designed water treatment program extends ZL-10T service life from 8 years (untreated) to 15+ years (treated). The minimum chemical regimen:

Algaecide: Apply at the basin inlet via chemical metering pump. Initial dose 100 ppm; maintenance dose 10-20 ppm weekly. Cost: USD 0.50/gram; annual usage approximately 400 grams for a single ZL-10T = USD 200/year.

Scale inhibitor: Phosphonate-based (HEDP or ATMP) at 5-10 ppm maintenance dose. Applied via chemical metering pump timed with makeup water addition. Cost: USD 0.30/gram; annual usage approximately 300 grams = USD 90/year.

Biocide (alternating with algaecide): Oxidizing biocide (sodium hypochlorite or bromine-based) shock dosed weekly at 1-2 ppm free chlorine equivalent. Controls biofilm that algaecide alone cannot eliminate. Cost: USD 0.10/gram; annual usage approximately 2 kg = USD 200/year.

Blowdown control: Install conductivity-controlled automated blowdown valve. Setpoint 2,200 µS/cm. Saves 30-50% makeup water versus continuous blowdown at fixed rate.

Total water treatment chemical cost: USD 490/year per ZL-10T. Labor for chemical system maintenance: USD 300/year. Total: USD 790/year.

Frequently Asked Questions

What water chemistry parameters does the ZL-10T require?

pH 6.5-9.0, calcium hardness <500 ppm as CaCO3, conductivity <2,500 µS/cm, total suspended solids <50 ppm. Operating outside these parameters accelerates scaling, biological growth, and corrosion.

How often should I clean the ZL-10T's fill media?

Quarterly visual inspection (15 minutes). Annual wash (3-4 hours) with descaling solution or commercial cooling tower cleaner. Apply algaecide at 50-100 ppm initial dose, 10-20 ppm maintenance dose.

What is the expected service life of the ZL-10T's fan motor?

The 0.37 kW fan motor uses sealed-for-life bearings rated for 50,000 hours. At 16 hr/day operation, this equates to 8.5 years. Annual motor service: amp draw verification, thermal discoloration check, V-belt tension adjustment.

How do I prevent freezing in cold climates?

Three options: (1) 1 kW basin heater (USD 150-220/year operating cost), (2) continuous winter circulation at reduced flow, (3) drain-down with 30% propylene glycol for residual piping. Freeze damage typically costs USD 1,500-3,000 versus USD 220/year in heater cost.

What chemicals are needed for water treatment?

Algaecide (USD 200/year), scale inhibitor (USD 90/year), biocide (USD 200/year) = USD 490/year chemical cost + USD 300/year labor. Total water treatment cost: USD 790/year per ZL-10T.

Authoritative References: CTI Maintenance Guideline (CTG-100) | ASHRAE Guideline 12 — Minimizing the Risk of Legionellosis

Explore other ZL-10T 10 Ton FRP Counter Flow Cooling Tower variants engineered for different applications:

Complementary Equipment for Closed-Loop Plastic Processing

Why ZL-10T from ZILLION

Zillion has supplied industrial cooling towers since 2009, with FRP counter flow construction as our standard since 2014. The ZL-10T's 7.81 m3/h flow at 5C range and 35.2 kW heat rejection cover the 10-ton process cooling capacity class at 0.37 kW fan power — the lowest power consumption per ton in our ZL series.

  • FRP shell and ABS fan construction, 15-20 year service life
  • Counter flow geometry with 5C approach at design WB 27C
  • Compact 940 x 940 mm footprint, 46 kg dry weight enables rooftop installation
  • CE certified for global deployment, 380V 3-phase 50Hz standard
  • 1-year warranty on all components

Contact: Leika Li, +86 185 2053 2504, Leika@gdzillion.cn. Factory: Building 103-B, Yi'an Industrial Park, Fenggang Town, Dongguan, Guangdong, China.

Send A Message
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.

Related Products

ZL-CT40 Industrial Round Cooling Tower 40T FRP
Industrial Fiberglass FRP GRP Counter Flow Cooling Tower Price Round FRP Cooling Tower 40T

Quick Specs: ZL-CT40 industrial round cooling tower with 40-ton cooling capacity, FRP material, counter-flow design, 1.5kW fan, CE certified. Best for industrial chiller systems and mid-scale manufacturing. The water cooling tower is a device used for cooling circulating water. By exchanging heat between hot water and air, the water temperature is reduced, thus realizing the repeated use of circulating water. Water cooling towers are widely used in industrial production, air conditioning systems and other fields, and are of great significance for saving water resources and reducing energy consumption.  

ZL-CT60 Round Shape Water Cooling Tower 60T
60T Round Shape Water Cooling Tower for Chiller Counter Flow Circular Cooling Tower Industrial Cooling System FRP Competitive Price

Quick Specs: ZL-CT60 round shape water cooling tower with 60-ton capacity, counter-flow design, FRP material, 1.5kW fan, CE certified. Best for industrial chiller systems and large-scale cooling. A water cooling tower is a device used for cooling industrial water or other liquids. Its main function is to cool down hot water through heat exchange between hot water and air so that the cooled water can be recycled.      

ZL-CT100 FRP Round Cooling Tower 100T
FRP Material 100 Ton Round Cooling Tower Price

Quick Specs: ZL-CT100 FRP round cooling tower with 100-ton cooling capacity, FRP material, 2.2kW fan, CE certified. Best for large-scale industrial cooling and high-capacity chiller systems. The counterflow cooling tower is a common type of cooling tower. It sprays hot water from top to bottom and air flows from bottom to top, enabling hot water and air to exchange heat in the packing, thereby reducing the water temperature. The counterflow cooling tower has the advantages of high cooling efficiency, compact structure and small floor area, and is widely used in industrial production, air conditioning and refrigeration and other fields.    

ZL-CT Square Drop Counter-Flow Cooling Tower FRP
Square Cooling Tower for Water Cooling: High - temperature Square Drop Counter - flow FRP and Open Cooling Towers

Quick Specs: ZL-CT square drop counter-flow cooling tower with FRP material, multiple capacity options, CE certified. Best for high-temperature industrial water cooling and open cooling tower applications. The square cooling tower has the advantages of small floor area, beautiful appearance, and convenient installation. It is widely used in fields such as air conditioning and refrigeration and industrial cooling, providing effective cooling guarantee for the normal operation of various equipments.      

ZL-CT Industrial Cooling Tower Multiple Types High Efficiency
Factory Direct High-Efficiency Industrial Cooling Tower Multiple Types Available

Quick Specs: ZL-CT factory-direct industrial cooling tower with multiple types and capacities, high-efficiency design, CE certified. Best for industrial cooling applications and large-scale manufacturing. A cooling tower dissipates heat from industrial or air - conditioning systems. Its working principle involves spraying hot water onto packing to form a water film, while air flow carries away heat from the water to lower its temperature. The cooled water is recyclable, saving water resources and reducing costs.​ There are various types, such as open and closed cooling towers. Open ones contact outside air directly, making water prone to contamination but with lower costs. Closed ones have water circulating in sealed pipes, ensuring cleaner water but usually at a higher price.​ Cooling towers play a key role in fields like power plants, chemical plants, and data centers, helping maintain system operation and improve energy utilization efficiency.​  

ZL-10T 10 ton FRP counter flow cooling tower, cfo procurement specification, 7.81 m3/h water flow, 0.37 kW motor, 35.2 kW heat rejection
ZL-10T Cooling Tower V3 CFO Procurement

The ZL-10T 10 Ton FRP Counter Flow Cooling Tower from Zillion delivers reliable cfo procurement performance. Key specifications include: ZL-10T 10 ton FRP counter flow cooling tower at USD 850 EXW 5-year TCO: USD 850 capex + USD 2,971/year opex Volume discounts: USD 765 (10+), USD 680 (50+), USD 595 (100+) Payment terms: T/T 30/70, L/C, Western Union, Alibaba Trade Assurance 18-month payback vs USD 4,500 air-cooled alternative Annual spare parts budget: USD 180 EXW Dongguan, lead time 7-15 days CE certified for global deployment Designed for industrial-grade cfo procurement applications, the ZL-10T combines proven FRP counter flow technology with precision-engineered components for 15-20 year service life. CE / ISO 9001:2015 certified. Contact Leika at Leika@gdzillion.cn for quotation.

ZL-10T 10 ton FRP counter flow cooling tower, epc contractor specification, 7.81 m3/h water flow, 0.37 kW motor, 35.2 kW heat rejection
ZL-10T Cooling Tower V5 EPC Contractor

The ZL-10T 10 Ton FRP Counter Flow Cooling Tower from Zillion delivers reliable epc contractor performance. Key specifications include: ZL-10T concrete pad: 600x600x150 mm C25/30 mix Wind load rating: 0.5 kPa for open terrain Piping connections: DN50 inlet/outlet, DN15 makeup, DN50 overflow 46 kg dry weight enables two-person ground-level installation Rooftop lift: portable gantry rated 250 kg Electrical: 380V 3-phase 50Hz, 1.2-1.5 A FLA VFD option for 30-60 Hz variable-speed operation 12-point pre-commissioning checklist Designed for industrial-grade epc contractor applications, the ZL-10T combines proven FRP counter flow technology with precision-engineered components for 15-20 year service life. CE / ISO 9001:2015 certified. Contact Leika at Leika@gdzillion.cn for quotation.

ZL-10T 10 ton FRP counter flow cooling tower, engineer technical specification, 7.81 m3/h water flow, 0.37 kW motor, 35.2 kW heat rejection
ZL-10T Cooling Tower V1 Engineer Technical

The ZL-10T 10 Ton FRP Counter Flow Cooling Tower from Zillion delivers reliable engineer technical performance. Key specifications include: ZL-10T 10 ton cooling capacity (35.2 kW heat rejection) Counter flow square FRP tower with 5C approach to wet-bulb 7.81 m3/h water flow at 5C range 0.37 kW fan motor (380V 3-phase 50Hz) 85 CMM airflow, 635 mm fan diameter Compact 940 x 1820 mm footprint, 46 kg dry weight 60 dB noise level for indoor/rooftop installation CE / ISO 9001:2015 certified, 1-year warranty Designed for industrial-grade engineer technical applications, the ZL-10T combines proven FRP counter flow technology with precision-engineered components for 15-20 year service life. CE / ISO 9001:2015 certified. Contact Leika at Leika@gdzillion.cn for quotation.