Home Refrigeration Machinery Cooling Tower Series

ZL-10T Cooling Tower V5 EPC Contractor

ZL-10T 10 ton FRP counter flow cooling tower, epc contractor specification, 7.81 m3/h water flow, 0.37 kW motor, 35.2 kW heat rejection

ZL-10T Cooling Tower V5 EPC Contractor

The ZL-10T 10 Ton FRP Counter Flow Cooling Tower from Zillion delivers reliable epc contractor performance. Key specifications include:

  • ZL-10T concrete pad: 600x600x150 mm C25/30 mix
  • Wind load rating: 0.5 kPa for open terrain
  • Piping connections: DN50 inlet/outlet, DN15 makeup, DN50 overflow
  • 46 kg dry weight enables two-person ground-level installation
  • Rooftop lift: portable gantry rated 250 kg
  • Electrical: 380V 3-phase 50Hz, 1.2-1.5 A FLA
  • VFD option for 30-60 Hz variable-speed operation
  • 12-point pre-commissioning checklist

Designed for industrial-grade epc contractor applications, the ZL-10T combines proven FRP counter flow technology with precision-engineered components for 15-20 year service life. CE / ISO 9001:2015 certified. Contact Leika at Leika@gdzillion.cn for quotation.

  • Brand:

    Dongguan Zillion
  • ItemNO:

    ZL-10T
  • Order(MOQ):

    1
  • Payment:

    T/T, L/C, Western Union, Alibaba Trade Assura
  • MarketPrice:

    $1050
  • price:

    $850/Set
  • ProductOrigin:

    China
  • Color:

    Blue + Gray (customizable)
  • ShippingPort:

    Shenzhen / Guangzhou
  • LeadTime:

    7-15 days
  • Weight:

    46
  • Size:

    High:2570mm Diameter:2900mm

ZL-10T 10 Ton Cooling Tower Installation Spec | Foundation Wind Load Piping Design

ZL-10T 10 Ton Counter Flow Square FRP Cooling Tower Quick Specifications

Parameter Value
Model ZL-10T
Cooling Capacity 10 RT (35.2 kW heat rejection)
Water Flow Rate 7.81 m3/h (130 L/min)
Cooling Range 5C (37C inlet to 32C outlet at design WB 27C)
Approach to Wet-Bulb 5C at design conditions
Fan Motor 0.37 kW (0.5 HP) 380V 3-phase 50Hz
Fan Diameter 635 mm axial
Air Flow Rate 85 CMM (50,920 m3/h)
Head Loss at Design Flow 13 kPa
Tower Dimensions (H x D) 1820 x 940 mm
Dry Weight 46 kg
Operating Weight (filled) 190 kg
Noise Level 60 dB(A) at 1 m
Tower Body Material FRP (Fiberglass Reinforced Plastic)
Fan Blade Material ABS plastic
Configuration Counter Flow Square
Voltage 380V 3-phase 50Hz (customizable 220V/415V)
Certifications CE / ISO 9001:2015
Warranty 1 year (consumables excluded)

Foundation Design: 600x600x150mm Concrete Pad, 25 kN/m² Bearing

The ZL-10T's 46 kg dry weight plus 190 kg operating weight (water-filled basin) creates a 236 kg total load on a 940x940 mm footprint — approximately 2.6 kN/m² ground pressure. Standard concrete pad specifications:

Pad dimensions: 600 × 600 × 150 mm (L × W × H) is the minimum for soil bearing capacity ≥25 kN/m². For weaker soils, increase pad area to 800 × 800 mm or 1,000 × 1,000 mm. Concrete: C25/30 mix (1:2:4 cement:sand:aggregate), reinforced with 6 mm mesh at 150 mm centers.

Mounting surface: Tower base flange bolts to embedded M10 × 80 mm anchor bolts (4 corners, 200 mm projection above pad). Use leveling shims (3 mm maximum stack height) to ensure tower is plumb — a 5 mm lean creates 0.5° misalignment, which the fan motor will fight against, increasing amp draw by 5-8%.

Drainage: Slope the pad surface 1-2% toward the basin drain side to direct overflow water to a floor drain or sump. Without proper pad drainage, overflow water pools under the tower, accelerating concrete degradation.

Wind Load Rating: 0.5 kPa for Open Terrain Installation

The ZL-10T's 1,820 mm height and 940 mm diameter present a frontal area of 0.94 m × 1.82 m = 1.71 m² to wind. For installation in open terrain (no surrounding buildings taller than the tower within 50 m), the design wind pressure is 0.5 kPa = 50 kgf/m²:

Lateral wind force on operating tower: 1.71 m² × 50 kgf/m² = 85.5 kgf at the tower's geometric center (height 910 mm). This force creates an overturning moment of 85.5 kgf × 0.91 m = 77.8 kgf·m about the base.

Required ballast: The 236 kg operating weight provides a restoring moment of 236 kgf × (0.94/2) = 110.9 kgf·m. The 77.8 kgf·m wind moment is comfortably resisted with a safety factor of 1.42. For taller installations or higher wind zones (coastal, mountain), consult the engineering tables in ZL-10T installation manual section 4.3.

For wind-exposed installations, additional tie-down straps to building structure are recommended. The ZL-10T base flange includes 4 anchor points designed for steel cable tie-downs (4 mm wire rope, breaking strength 1,800 kgf).

Piping Connections: DN50 Inlet, DN50 Outlet, DN15 Makeup, DN50 Overflow

The ZL-10T's four water connections are flanged DN50 (2 inch) PVC-compatible fittings:

Inlet (hot water from chiller condenser): DN50 flange, mounted on the top water distribution header. Schedule 80 PVC or carbon steel piping recommended. Design flow 7.81 m³/h requires minimum 40 mm internal diameter (DN50 provides 50 mm — 25% margin).

Outlet (cooled water to chiller): DN50 flange, mounted on the basin side wall. Includes integrated stainless steel strainer (1.5 mm perforation) to prevent debris from entering the chiller.

Makeup water: DN15 (1/2 inch) threaded connection on the basin side wall. Connect to plant water supply through a float valve (supplied). Float valve setting: water level 50 mm below overflow level.

Overflow: DN50 connection at the basin top, piped to a floor drain or indirect waste receptor. Prevents basin overflow during pump failure or makeup valve malfunction.

Drain: DN50 bottom-mounted ball valve for basin drain-down during maintenance. Connect to floor drain via indirect waste pipe (air gap).

Crane and Rigging: 46 kg Dry Weight Allows Manual Installation

The ZL-10T's 46 kg dry weight is a significant advantage for installation logistics. Three installation scenarios are common:

Scenario 1 — Ground level installation: Two-person team can lift the tower directly from delivery truck onto prepared pad. No crane required. Typical time: 30 minutes for positioning + 2 hours for piping and electrical.

Scenario 2 — Rooftop installation (2-3 floor building): Use a portable gantry or chain hoist to lift the tower to the roof. With 46 kg dry weight, a single-rope manual hoist (rated 250 kg) is sufficient. Typical time: 1 hour for lift + 4 hours for piping and electrical.

Scenario 3 — High-rise rooftop (5+ floors): Use a small mobile crane (1-2 ton capacity) or building service elevator. With 46 kg dry weight, the tower can often be moved without disassembly — even if the elevator is rated only 100 kg per trip, the tower fits in 2-3 elevator trips after subassembly. Typical time: 2 hours for rigging + 6 hours for piping and electrical.

For all scenarios, lifting points are integrated into the tower's top frame — standard rigging hooks engage the 4 lift points for balanced lift.

Electrical: 380V 3-Phase, 0.37 kW, 1.5A Full Load

The ZL-10T's fan motor requires 380V 3-phase 50Hz power supply. For installations where 3-phase is not available, single-phase operation requires a phase converter (typically a 1.5 kVA rotary or static converter).

Motor specification: 0.37 kW (0.5 HP), 380V ±3-phase, 50 Hz, 1,440 rpm, IP55 protection class, Class F insulation. Full load current: 1.2-1.5 amps (depending on power factor and motor manufacturer).

Overload protection: Thermal overload relay setting: 1.5 amps (1.0 × FLA). Phase failure relay required for installations with unstable 3-phase supply (common in rural or generator-backed installations).

Wiring: 3 × 1.5 mm² PVC-insulated copper cable from distribution board to motor junction box. Maximum cable run: 50 m without derating. For runs exceeding 50 m, upgrade to 3 × 2.5 mm² to limit voltage drop to <3%.

Control: Simple on/off switch with thermal overload. For variable-speed operation (energy saving at partial load), a VFD rated 0.75 kW (next size up) provides 30-60 Hz speed range.

Pre-Commissioning Checklist: 12 Inspection Points

Before initial startup, the EPC contractor completes this 12-point pre-commissioning checklist:

1. ✓ Pad surface level within ±3 mm/m (use 1 m straight edge). 2. ✓ Anchor bolts tight (torque to 35 Nm). 3. ✓ Tower plumb within 2 mm vertical deviation over full height. 4. ✓ Inlet/outlet piping flushed clean (no debris). 5. ✓ Makeup float valve operational, no leaks. 6. ✓ Drain valve closed, no leaks. 7. ✓ Overflow pipe unobstructed. 8. ✓ Motor rotation correct (verify arrow on fan housing matches). 9. ✓ Motor amp draw at full load within 10% of nameplate. 10. ✓ Electrical grounding verified (<10 ohms to ground). 11. ✓ Basin filled to operating level (50 mm below overflow). 12. ✓ Water treatment chemicals dosed per maintenance manual.

Document each check on the commissioning report form. Sign-off by EPC site engineer and customer's facility engineer required before final handover.

Frequently Asked Questions

What foundation is required for the ZL-10T?

600 × 600 × 150 mm concrete pad (C25/30 mix, 6 mm mesh at 150 mm centers). Four M10 × 80 mm anchor bolts at corners. Pad level within ±3 mm/m. Pad slope 1-2% toward drain side.

What is the wind load rating of the ZL-10T?

0.5 kPa for open terrain installation. Lateral wind force 85.5 kgf at tower's geometric center (height 910 mm). Restoring moment from 236 kg operating weight: 110.9 kgf·m versus wind moment 77.8 kgf·m (safety factor 1.42).

What are the piping connections on the ZL-10T?

DN50 inlet (top), DN50 outlet (basin side with strainer), DN15 makeup water (float valve), DN50 overflow, DN50 drain (ball valve). Schedule 80 PVC or carbon steel recommended.

How is the ZL-10T lifted into place?

46 kg dry weight allows two-person ground-level installation. For rooftop: portable gantry or chain hoist (rated 250 kg). For high-rise: 1-2 ton mobile crane. Four integrated lift points on the tower's top frame.

What electrical supply does the ZL-10T require?

380V 3-phase 50Hz, 1.2-1.5 A full load current, 0.37 kW motor. Thermal overload set at 1.5 A. Wiring: 3 × 1.5 mm² PVC copper cable (50 m max), upgrade to 3 × 2.5 mm² for longer runs. VFD option for variable-speed operation.

Authoritative References: ASCE 7-22 Minimum Design Loads for Buildings | ACI 318 Building Code Requirements for Structural Concrete

Explore other ZL-10T 10 Ton FRP Counter Flow Cooling Tower variants engineered for different applications:

Complementary Equipment for Closed-Loop Plastic Processing

Why ZL-10T from ZILLION

Zillion has supplied industrial cooling towers since 2009, with FRP counter flow construction as our standard since 2014. The ZL-10T's 7.81 m3/h flow at 5C range and 35.2 kW heat rejection cover the 10-ton process cooling capacity class at 0.37 kW fan power — the lowest power consumption per ton in our ZL series.

  • FRP shell and ABS fan construction, 15-20 year service life
  • Counter flow geometry with 5C approach at design WB 27C
  • Compact 940 x 940 mm footprint, 46 kg dry weight enables rooftop installation
  • CE certified for global deployment, 380V 3-phase 50Hz standard
  • 1-year warranty on all components

Contact: Leika Li, +86 185 2053 2504, Leika@gdzillion.cn. Factory: Building 103-B, Yi'an Industrial Park, Fenggang Town, Dongguan, Guangdong, China.

Send A Message
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.

Related Products

ZL-CT40 Industrial Round Cooling Tower 40T FRP
Industrial Fiberglass FRP GRP Counter Flow Cooling Tower Price Round FRP Cooling Tower 40T

Quick Specs: ZL-CT40 industrial round cooling tower with 40-ton cooling capacity, FRP material, counter-flow design, 1.5kW fan, CE certified. Best for industrial chiller systems and mid-scale manufacturing. The water cooling tower is a device used for cooling circulating water. By exchanging heat between hot water and air, the water temperature is reduced, thus realizing the repeated use of circulating water. Water cooling towers are widely used in industrial production, air conditioning systems and other fields, and are of great significance for saving water resources and reducing energy consumption.  

ZL-CT60 Round Shape Water Cooling Tower 60T
60T Round Shape Water Cooling Tower for Chiller Counter Flow Circular Cooling Tower Industrial Cooling System FRP Competitive Price

Quick Specs: ZL-CT60 round shape water cooling tower with 60-ton capacity, counter-flow design, FRP material, 1.5kW fan, CE certified. Best for industrial chiller systems and large-scale cooling. A water cooling tower is a device used for cooling industrial water or other liquids. Its main function is to cool down hot water through heat exchange between hot water and air so that the cooled water can be recycled.      

ZL-CT100 FRP Round Cooling Tower 100T
FRP Material 100 Ton Round Cooling Tower Price

Quick Specs: ZL-CT100 FRP round cooling tower with 100-ton cooling capacity, FRP material, 2.2kW fan, CE certified. Best for large-scale industrial cooling and high-capacity chiller systems. The counterflow cooling tower is a common type of cooling tower. It sprays hot water from top to bottom and air flows from bottom to top, enabling hot water and air to exchange heat in the packing, thereby reducing the water temperature. The counterflow cooling tower has the advantages of high cooling efficiency, compact structure and small floor area, and is widely used in industrial production, air conditioning and refrigeration and other fields.    

ZL-CT Square Drop Counter-Flow Cooling Tower FRP
Square Cooling Tower for Water Cooling: High - temperature Square Drop Counter - flow FRP and Open Cooling Towers

Quick Specs: ZL-CT square drop counter-flow cooling tower with FRP material, multiple capacity options, CE certified. Best for high-temperature industrial water cooling and open cooling tower applications. The square cooling tower has the advantages of small floor area, beautiful appearance, and convenient installation. It is widely used in fields such as air conditioning and refrigeration and industrial cooling, providing effective cooling guarantee for the normal operation of various equipments.      

ZL-CT Industrial Cooling Tower Multiple Types High Efficiency
Factory Direct High-Efficiency Industrial Cooling Tower Multiple Types Available

Quick Specs: ZL-CT factory-direct industrial cooling tower with multiple types and capacities, high-efficiency design, CE certified. Best for industrial cooling applications and large-scale manufacturing. A cooling tower dissipates heat from industrial or air - conditioning systems. Its working principle involves spraying hot water onto packing to form a water film, while air flow carries away heat from the water to lower its temperature. The cooled water is recyclable, saving water resources and reducing costs.​ There are various types, such as open and closed cooling towers. Open ones contact outside air directly, making water prone to contamination but with lower costs. Closed ones have water circulating in sealed pipes, ensuring cleaner water but usually at a higher price.​ Cooling towers play a key role in fields like power plants, chemical plants, and data centers, helping maintain system operation and improve energy utilization efficiency.​  

ZL-10T 10 ton FRP counter flow cooling tower, cfo procurement specification, 7.81 m3/h water flow, 0.37 kW motor, 35.2 kW heat rejection
ZL-10T Cooling Tower V3 CFO Procurement

The ZL-10T 10 Ton FRP Counter Flow Cooling Tower from Zillion delivers reliable cfo procurement performance. Key specifications include: ZL-10T 10 ton FRP counter flow cooling tower at USD 850 EXW 5-year TCO: USD 850 capex + USD 2,971/year opex Volume discounts: USD 765 (10+), USD 680 (50+), USD 595 (100+) Payment terms: T/T 30/70, L/C, Western Union, Alibaba Trade Assurance 18-month payback vs USD 4,500 air-cooled alternative Annual spare parts budget: USD 180 EXW Dongguan, lead time 7-15 days CE certified for global deployment Designed for industrial-grade cfo procurement applications, the ZL-10T combines proven FRP counter flow technology with precision-engineered components for 15-20 year service life. CE / ISO 9001:2015 certified. Contact Leika at Leika@gdzillion.cn for quotation.

ZL-10T 10 ton FRP counter flow cooling tower, maintenance tech specification, 7.81 m3/h water flow, 0.37 kW motor, 35.2 kW heat rejection
ZL-10T Cooling Tower V4 Maintenance Tech

The ZL-10T 10 Ton FRP Counter Flow Cooling Tower from Zillion delivers reliable maintenance tech performance. Key specifications include: ZL-10T water chemistry: pH 6.5-9.0, Ca hardness <500 ppm Conductivity <2,500 uS/cm, TSS <50 ppm Quarterly fill media visual inspection (15 minutes) Annual wash with descaling solution (3-4 hours) Fan motor 50,000 hour bearing life (8.5 years at 16 hr/day) Winter freeze protection: basin heater USD 220/year operating Annual water treatment chemical cost: USD 490 Drift eliminator replacement: 5-year cycle Designed for industrial-grade maintenance tech applications, the ZL-10T combines proven FRP counter flow technology with precision-engineered components for 15-20 year service life. CE / ISO 9001:2015 certified. Contact Leika at Leika@gdzillion.cn for quotation.

ZL-10T 10 ton FRP counter flow cooling tower, engineer technical specification, 7.81 m3/h water flow, 0.37 kW motor, 35.2 kW heat rejection
ZL-10T Cooling Tower V1 Engineer Technical

The ZL-10T 10 Ton FRP Counter Flow Cooling Tower from Zillion delivers reliable engineer technical performance. Key specifications include: ZL-10T 10 ton cooling capacity (35.2 kW heat rejection) Counter flow square FRP tower with 5C approach to wet-bulb 7.81 m3/h water flow at 5C range 0.37 kW fan motor (380V 3-phase 50Hz) 85 CMM airflow, 635 mm fan diameter Compact 940 x 1820 mm footprint, 46 kg dry weight 60 dB noise level for indoor/rooftop installation CE / ISO 9001:2015 certified, 1-year warranty Designed for industrial-grade engineer technical applications, the ZL-10T combines proven FRP counter flow technology with precision-engineered components for 15-20 year service life. CE / ISO 9001:2015 certified. Contact Leika at Leika@gdzillion.cn for quotation.